Modbus – KWh meter – Socomec Countis E03

De COUNTIS E0x is een modulaire meter voor actieve elektrische energie met aflezing van kWh. Dit toestel laat een rechtstreekse aansluiting toe tot 32A.

Onder andere uit te lezen met Modbus RS485


Foto’s


Modbus registers

Product identification

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
50000 0xC350 Info 66 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
50000 0xC350 4 “SOCO” STRING_16
50004 0xC354 1 Product order ID (Countis:100, Protection:200, Atys:300, Diris:400) U16
50005 0xC355 1 Product ID (EX: 1000 ATS3) U16
50006 0xC356 1 JBUS Table Version (EX: 101 Version 1.01) U16
50007 0xC357 1 Product software version (EX: 100 Version 1.00) U16
50008 0xC358 1 Serial_AA_SS U16_HEX
50009 0xC359 1 Serial_SST_L U16_HEX
50010 0xC35A 1 Serial_order U16
50011 0xC35B 2 Serial_Reserve U32
50013 0xC35D 4 See “Code table” tab for more details U64_HEX
50017 0xC361 1 Reserved
50018 0xC362 1 Product version (Major) U16
50019 0xC363 1 Product version (Minor) U16
50020 0xC364 1 Reserved
50021 0xC365 1 Reserved
50022 0xC366 3 Reserved
50025 0xC369 1 Reserved
50026 0xC36A 1 Reserved
50027 0xC36B 1 Reserved
50028 0xC36C 1 Reserved
50029 0xC36D 1 Reserved
50030 0xC36E 4 Product VLO (EX : “880100”) STRING_NORM
50034 0xC372 4 Reserved
50038 0xC376 4 Reserved
50042 0xC37A 8 Vendor name (EX : “SOCOMEC”) STRING_NORM
50050 0xC382 8 Product name (EX : “DIRIS A40R”) STRING_NORM
50058 0xC38A 8 Extended name STRING_NORM

 

Common settings

 

Modbus Parameters

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
36865 0x9001 Settings 3 NONE READ | WRITE | WRITE_MANY READ | WRITE | WRITE_MANY

 

Dec address Hex address Words count Description Unit Data type
36865 0x9001 1 RS485 Address : 1 – 247 U16
36866 0x9002 1 RS485 Baud rate :
0 : 1200
1 : 2400
2 : 4800
3 : 9600
4 : 19200
5 : 38400
U16
36867 0x9003 1 RS485 Parity :
0 : No Parity
1 : Odd
2 : Even
U16

 

Actions

 

Action system

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57856 0xE200 Commands 1 NONE WRITE WRITE

 

Dec address Hex address Words count Description Unit Data type
57856 0xE200 1 Action :
0xA1 : Product Configuration storage
0xB2 : Product reset
U8_HEX

 

Value reset

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
57888 0xE220 Commands 5 NONE WRITE WRITE

 

Dec address Hex address Words count Description Unit Data type
57888 0xE220 1 Reserved
57889 0xE221 1 Reserved
57890 0xE222 1 Reset :
0x0001 : Partial Ea+
0x0002 : Partial Er+
0x0004 : Partial Eap
0x0008 : Partial Ea-
0x0010 : Partial Er-
U16_HEX
57891 0xE223 1 Reserved
57892 0xE224 1 Reserved

Metrology Affected by current and voltage transformers

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
50512 0xC550 Info 62 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
50512 0xC550 2 Reserved
50514 0xC552 2 Reserved
50516 0xC554 2 Reserved
50518 0xC556 2 Reserved
50520 0xC558 2 Simple voltage : V1 V / 100 U32
50522 0xC55A 2 Reserved
50524 0xC55C 2 Reserved
50526 0xC55E 2 Frequency : F Hz / 100 U32
50528 0xC560 2 Current : I1 A / 1000 U32
50530 0xC562 2 Reserved
50532 0xC564 2 Reserved
50534 0xC566 2 Reserved
50536 0xC568 2 Sum Active Power +/- : P W / 0.1 S32
50538 0xC56A 2 Sum Reactive Power +/- : Q var / 0.1 S32
50540 0xC56C 2 Sum Apparent Power : S VA / 0.1 U32
50542 0xC56E 2 Sum Power Factor : -: leading et + : lagging : PF – / 1000 S32
50544 0xC570 2 Active Power phase 1 +/- : P1 W / 0.1 S32
50546 0xC572 2 Reserved
50548 0xC574 2 Reserved
50550 0xC576 2 Reactive Power phase 1 +/- : Q1 var / 0.1 S32
50552 0xC578 2 Reserved
50554 0xC57A 2 Reserved
50556 0xC57C 2 Apparent Power phase 1 : S1 VA / 0.1 U32
50558 0xC57E 2 Reserved
50560 0xC580 2 Reserved
50562 0xC582 2 Power Factor phase 1 -: leading and + : lagging : PF1 – / 1000 S32
50564 0xC584 2 Reserved
50566 0xC586 2 Reserved
50568 0xC588 2 Reserved
50570 0xC58A 2 Reserved
50572 0xC58C 2 Reserved

 

Metrology No Affected by current and voltage transformers

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
51280 0xC850 Info 36 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
51280 0xC850 1 Reserved
51281 0xC851 1 Reserved
51282 0xC852 1 Reserved
51283 0xC853 1 Reserved
51284 0xC854 1 Simple voltage : V1 V / 100 U16
51285 0xC855 1 Reserved
51286 0xC856 1 Reserved
51287 0xC857 1 Frequency : F Hz / 100 U16
51288 0xC858 1 Reserved
51289 0xC859 1 Reserved
51290 0xC85A 1 Reserved
51291 0xC85B 1 Reserved
51292 0xC85C 1 Reserved
51293 0xC85D 1 Reserved
51294 0xC85E 1 Reserved
51295 0xC85F 1 Sum power factor : -: leading and + : lagging : PF – / 1000 S16
51296 0xC860 1 Reserved
51297 0xC861 1 Reserved
51298 0xC862 1 Reserved
51299 0xC863 1 Reserved
51300 0xC864 1 Reserved
51301 0xC865 1 Reserved
51302 0xC866 1 Reserved
51303 0xC867 1 Reserved
51304 0xC868 1 Reserved
51305 0xC869 1 Power Factor phase 1 -: leading and + : lagging : PF1 – / 1000 S16
51306 0xC86A 1 Reserved
51307 0xC86B 1 Reserved
51308 0xC86C 1 Reserved
51309 0xC86D 1 Reserved
51310 0xC86E 1 Reserved
51311 0xC86F 1 Total Positive Active Energy (no resetable) : Ea+ Wh / 1E-06 U16
51312 0xC870 1 Total Positive Reactive Energy (no resetable) : Er + varh / 1E-06 U16
51313 0xC871 1 Total Negative Active Energy (no resetable) : Ea- Wh / 1E-06 U16
51314 0xC872 1 Total Negative Reactive Energy (no resetable) : Er – varh / 1E-06 U16
51315 0xC873 1 Reserved

 

Energies

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
50768 0xC650 Info 65 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
50768 0xC650 2 Reserved
50770 0xC652 2 Total Positive Active Energy (no resetable) : Ea+ Wh / 0.001 U32
50772 0xC654 2 Total Positive Reactive Energy (no resetable) : Er + varh / 0.001 U32
50774 0xC656 2 Total Apparent Energy (no resetable) : Eap VAh / 0.001 U32
50776 0xC658 2 Total Negative Active Energy (no resetable) : Ea- Wh / 0.001 U32
50778 0xC65A 2 Total Negative Reactive Energy (no resetable) : Er – varh / 0.001 U32
50780 0xC65C 2 Partial Positive Active Energy: Ea+ Wh / 0.001 U32
50782 0xC65E 2 Partial Positive Reactive Energy: Er + varh / 0.001 U32
50784 0xC660 2 Partial Apparent Energy : Eap VAh / 0.001 U32
50786 0xC662 2 Partial Negative Active Energy : Ea- Wh / 0.001 U32
50788 0xC664 2 Partial Negative Reactive Energy : Er – varh / 0.001 U32
50790 0xC666 2 Reserved
50792 0xC668 2 Reserved
50794 0xC66A 2 Reserved
50796 0xC66C 2 Reserved
50798 0xC66E 2 Reserved
50800 0xC670 2 Reserved
50802 0xC672 2 Reserved
50804 0xC674 2 Reserved
50806 0xC676 2 Reserved
50808 0xC678 2 Reserved
50810 0xC67A 2 Reserved
50812 0xC67C 2 Reserved
50814 0xC67E 2 Reserved
50816 0xC680 2 Reserved
50818 0xC682 2 Reserved
50820 0xC684 2 Reserved
50822 0xC686 2 Reserved
50824 0xC688 2 Reserved
50826 0xC68A 2 Reserved
50828 0xC68C 1 Reserved
50829 0xC68D 1 Reserved
50830 0xC68E 1 Reserved
50831 0xC68F 1 Reserved
50832 0xC690 1 Reserved

 

Energies in Unit/100

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
50944 0xC700 Info 65 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
50944 0xC700 2 Reserved
50946 0xC702 2 Total Positive Active Energy (no resetable) : Ea+ Wh / 0.1 U32
50948 0xC704 2 Total Positive Reactive Energy (no resetable) : Er + varh / 0.1 U32
50950 0xC706 2 Reserved
50952 0xC708 2 Total Negative Active Energy (no resetable) : Ea- Wh / 0.1 U32
50954 0xC70A 2 Total Negative Reactive Energy (no resetable) : Er – varh / 0.1 U32
50956 0xC70C 2 Partial Positive Active Energy: Ea+ Wh / 0.1 U32
50958 0xC70E 2 Partial Positive Reactive Energy: Er + varh / 0.1 U32
50960 0xC710 2 Reserved
50962 0xC712 2 Partial Negative Active Energy : Ea- Wh / 0.1 U32
50964 0xC714 2 Partial Negative Reactive Energy : Er – varh / 0.1 U32
50966 0xC716 2 Reserved
50968 0xC718 2 Reserved
50970 0xC71A 2 Reserved
50972 0xC71C 2 Reserved
50974 0xC71E 2 Reserved
50976 0xC720 2 Reserved
50978 0xC722 2 Reserved
50980 0xC724 2 Reserved
50982 0xC726 2 Reserved
50984 0xC728 2 Reserved
50986 0xC72A 2 Reserved
50988 0xC72C 2 Reserved
50990 0xC72E 2 Reserved
50992 0xC730 2 Reserved
50994 0xC732 2 Reserved
50996 0xC734 2 Reserved
50998 0xC736 2 Reserved
51000 0xC738 2 Reserved
51002 0xC73A 2 Reserved
51004 0xC73C 1 Reserved
51005 0xC73D 1 Reserved
51006 0xC73E 1 Reserved
51007 0xC73F 1 Reserved
51008 0xC740 1 Reserved

 

Energies per tariff

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
50848 0xC6A0 Info 50 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
50848 0xC6A0 1 1 >= Tariff number <= 2 U8
50849 0xC6A1 1 Tariff number in progress ( 1 to 2 ) U8
50850 0xC6A2 2 Positive Active Energies 1 Wh / 0.001 U32
50852 0xC6A4 2 Positive Active Energies 2 Wh / 0.001 U32
50854 0xC6A6 2 Reserved
50856 0xC6A8 2 Reserved
50858 0xC6AA 2 Reserved
50860 0xC6AC 2 Reserved
50862 0xC6AE 2 Reserved
50864 0xC6B0 2 Reserved
50866 0xC6B2 2 Positive Reactive Enegies 1 varh / 0.001 U32
50868 0xC6B4 2 Positive Reactive Enegies 2 varh / 0.001 U32
50870 0xC6B6 2 Reserved
50872 0xC6B8 2 Reserved
50874 0xC6BA 2 Reserved
50876 0xC6BC 2 Reserved
50878 0xC6BE 2 Reserved
50880 0xC6C0 2 Reserved
50882 0xC6C2 2 Time Counter 1 h / 100 U32
50884 0xC6C4 2 Time Counter 2 h / 100 U32
50886 0xC6C6 2 Reserved
50888 0xC6C8 2 Reserved
50890 0xC6CA 2 Reserved
50892 0xC6CC 2 Reserved
50894 0xC6CE 2 Reserved
50896 0xC6D0 2 Reserved

 

Energies per tariff in Unit/100

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
51200 0xC800 Info 50 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
51200 0xC800 1 1 >= Tariff number <= 2 U8
51201 0xC801 1 Tariff number in progress ( 1 to 2 ) U8
51202 0xC802 2 Positive Active Energies 1 Wh / 0.1 U32
51204 0xC804 2 Positive Active Energies 2 Wh / 0.1 U32
51206 0xC806 2 Reserved
51208 0xC808 2 Reserved
51210 0xC80A 2 Reserved
51212 0xC80C 2 Reserved
51214 0xC80E 2 Reserved
51216 0xC810 2 Reserved
51218 0xC812 2 Positive Reactive Enegies 1 varh / 0.1 U32
51220 0xC814 2 Positive Reactive Enegies 2 varh / 0.1 U32
51222 0xC816 2 Reserved
51224 0xC818 2 Reserved
51226 0xC81A 2 Reserved
51228 0xC81C 2 Reserved
51230 0xC81E 2 Reserved
51232 0xC820 2 Reserved
51234 0xC822 2 Time Counter 1 h / 100 U32
51236 0xC824 2 Time Counter 2 h / 100 U32
51238 0xC826 2 Reserved
51240 0xC828 2 Reserved
51242 0xC82A 2 Reserved
51244 0xC82C 2 Reserved
51246 0xC82E 2 Reserved
51248 0xC830 2 Reserved

 

Energy measurement – Total

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
25984 0x6580 Info 66 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
25984 0x6580 1 Reserved
25985 0x6581 2 Reserved
25987 0x6583 2 Total Positive active Energy : Ea+ Wh / 0.001 U32
25989 0x6585 1 Total Residual positive active Energy : rEa+ Wh / 10 U16
25990 0x6586 2 Total Negative active Energy : Ea- Wh / 0.001 U32
25992 0x6588 1 Total Residual negative active Energy : rEa- Wh / 10 U16
25993 0x6589 2 Total Positive reactive Energy : Er+ varh / 0.001 U32
25995 0x658B 1 Total Residual positive reactive Energy : rEr+ varh / 10 U16
25996 0x658C 2 Total Negative reactive Energy : Er- varh / 0.001 U32
25998 0x658E 1 Total Residual negative reactive Energy : rEr- varh / 10 U16
25999 0x658F 2 Total Apparent Energy : Eap VAh / 0.001 U32
26001 0x6591 1 Total Residual apparent Energy : rEap VAh / 10 U16
26002 0x6592 2 Total positive lagging reactive Energy : Er+ (lagging) varh / 0.001 U32
26004 0x6594 1 Total residual positive lagging reactive Energy : rEr+ (lagging) varh / 10 U16
26005 0x6595 2 Total negative lagging reactive Energy : Er- (lagging) varh / 0.001 U32
26007 0x6597 1 Total residual negative lagging reactive Energy : rEr- (lagging) varh / 10 U16
26008 0x6598 2 Total positive leading reactive Energy : Er+ (leading) varh / 0.001 U32
26010 0x659A 1 Total residual positive leading reactive Energy : rEr+ (leading) varh / 10 U16
26011 0x659B 2 Total negative leading reactive Energy : Er- (leading) varh / 0.001 U32
26013 0x659D 1 Total residual negative leading reactive Energy : rEr- (leading) varh / 10 U16
26014 0x659E 2 Reserved
26016 0x65A0 2 Reserved
26018 0x65A2 1 Reserved
26019 0x65A3 2 Reserved
26021 0x65A5 1 Reserved
26022 0x65A6 2 Reserved
26024 0x65A8 1 Reserved
26025 0x65A9 2 Reserved
26027 0x65AB 1 Reserved
26028 0x65AC 2 Reserved
26030 0x65AE 1 Reserved
26031 0x65AF 2 Reserved
26033 0x65B1 2 Reserved
26035 0x65B3 2 Reserved
26037 0x65B5 1 Reserved
26038 0x65B6 2 Reserved
26040 0x65B8 1 Reserved
26041 0x65B9 2 Reserved
26043 0x65BB 1 Reserved
26044 0x65BC 2 Reserved
26046 0x65BE 1 Reserved
26047 0x65BF 2 Reserved
26049 0x65C1 1 Reserved

 

Tariff meter (total) – Total (1st Part)

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
26368 0x6700 Info 33 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
26368 0x6700 1 Tariff number in progress (Available for 1st,2nd and 3rd Part Below)
1 : Tariff 1
2 : Tariff 2
U16
26369 0x6701 2 T1 – Ea+ Wh / 0.001 U32
26371 0x6703 2 T2 – Ea+ Wh / 0.001 U32
26373 0x6705 2 Reserved
26375 0x6707 2 Reserved
26377 0x6709 2 Reserved
26379 0x670B 2 Reserved
26381 0x670D 2 Reserved
26383 0x670F 2 Reserved
26385 0x6711 2 T1 – Ea- Wh / 0.001 U32
26387 0x6713 2 T2 – Ea- Wh / 0.001 U32
26389 0x6715 2 Reserved
26391 0x6717 2 Reserved
26393 0x6719 2 Reserved
26395 0x671B 2 Reserved
26397 0x671D 2 Reserved
26399 0x671F 2 Reserved

 

Tariff meter (total) – Total (2nd Part)

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
26401 0x6721 Info 96 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
26401 0x6721 2 T1 – Er+ varh / 0.001 U32
26403 0x6723 2 T2 – Er+ varh / 0.001 U32
26405 0x6725 2 Reserved
26407 0x6727 2 Reserved
26409 0x6729 2 Reserved
26411 0x672B 2 Reserved
26413 0x672D 2 Reserved
26415 0x672F 2 Reserved
26417 0x6731 2 T1 – Er+ (lagging) varh / 0.001 U32
26419 0x6733 2 T2 – Er+ (lagging) varh / 0.001 U32
26421 0x6735 2 Reserved
26423 0x6737 2 Reserved
26425 0x6739 2 Reserved
26427 0x673B 2 Reserved
26429 0x673D 2 Reserved
26431 0x673F 2 Reserved
26433 0x6741 2 T1 – Er+ (leading) varh / 0.001 U32
26435 0x6743 2 T2 – Er+ (leading) varh / 0.001 U32
26437 0x6745 2 Reserved
26439 0x6747 2 Reserved
26441 0x6749 2 Reserved
26443 0x674B 2 Reserved
26445 0x674D 2 Reserved
26447 0x674F 2 Reserved
26449 0x6751 2 T1 – Er- varh / 0.001 U32
26451 0x6753 2 T2 – Er- varh / 0.001 U32
26453 0x6755 2 Reserved
26455 0x6757 2 Reserved
26457 0x6759 2 Reserved
26459 0x675B 2 Reserved
26461 0x675D 2 Reserved
26463 0x675F 2 Reserved
26465 0x6761 2 T1 – Er- (lagging) varh / 0.001 U32
26467 0x6763 2 T2 – Er- (lagging) varh / 0.001 U32
26469 0x6765 2 Reserved
26471 0x6767 2 Reserved
26473 0x6769 2 Reserved
26475 0x676B 2 Reserved
26477 0x676D 2 Reserved
26479 0x676F 2 Reserved
26481 0x6771 2 T1 – Er- (leading) varh / 0.001 U32
26483 0x6773 2 T2 – Er- (leading) varh / 0.001 U32
26485 0x6775 2 Reserved
26487 0x6777 2 Reserved
26489 0x6779 2 Reserved
26491 0x677B 2 Reserved
26493 0x677D 2 Reserved
26495 0x677F 2 Reserved

 

Tariff meter (total) – Total (3rd Part)

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
26497 0x6781 Info 16 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
26497 0x6781 2 T1 – Eap VAh / 0.001 U32
26499 0x6783 2 T2 – Eap VAh / 0.001 U32
26501 0x6785 2 Reserved
26503 0x6787 2 Reserved
26505 0x6789 2 Reserved
26507 0x678B 2 Reserved
26509 0x678D 2 Reserved
26511 0x678F 2 Reserved

 

Current without CT

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
40576 0x9E80 Info 6 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
40576 0x9E80 2 Current: I1 A / 1000 U32
40578 0x9E82 2 Reserved
40580 0x9E84 2 Reserved

 

Energy index

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
36868 0x9004 Info 2 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
36868 0x9004 2 Active Energy Wh U32

 

Set Tariff

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
40480 0x9E20 Commands 2 NONE WRITE WRITE

 

Dec address Hex address Words count Description Unit Data type
40480 0x9E20 1 Reserved
40481 0x9E21 1 Tariff Number to set U8

 

Partial Energies Reset

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
40512 0x9E40 Commands 1 NONE WRITE WRITE

 

Dec address Hex address Words count Description Unit Data type
40512 0x9E40 1 Reset
0x20 : Partial Energies
U8_HEX

 

Industrialization

 

Indus Mode and MID status

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
40544 0x9E60 Info 2 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
40544 0x9E60 1 Indus Mode (0: indus mode disabled, 1: indus mode enabled) U8
40545 0x9E61 1 MID status (0: non-MID product, 1: MID product U8

 

COM Board Product ID

Dec start address Hex start address Type Size Lock level Locked fcts Unlocked fcts
40608 0x9EA0 Info 1 NONE READ READ

 

Dec address Hex address Words count Description Unit Data type
40608 0x9EA0 1 Product ID :0x01: E3x/E4x COM Board0x02: E63 COM Board U8


Voorbeeld uitlezen

Fabriek gegevens
Standaard adres: 1
Baud rate: 9600